PART
1 - GENERA
1.01 SCOPE
The Contractor, as part of the work of this section,
shall coordinate, receive connect and place into
operation all equipment. The Contractor shall
furnish all conduit, wire, connectors, hardware,
pipe, fittings, and other incidental items necessary
for the complete and properly functioning.
The Contractor shall coordinate the mounting of
the utility boxes among all associated trades.
Provide complete assembly for electrical power1
telephone, data, air, water and drain in a concrete
tight, water tight, non-corrosive enclosure suitable
for flush floor installation in high vehicular
traffic areas with very high concentrated loads.
1.02 MANUFACTURER'S SERVICES
A. Shop drawings shall be submitted for
approval within 30 days after receipt of purchase
order. No fabrication of equipment is to proceed
prior to approval of these drawings. Submittal
package shall contain six (6) sets of the following:
1. Cover Sheet.
2. Complete Bill of Materials.
3. Catalog Cut Sheets.
4. Shop Drawings detailing all mechanical and
electrical equipment including internal wiring,
and physical dimensions. Include all items supplied
for electrical, air, water, and drainage.
B. Shop drawings shall be submitted from standard
product drawings modified for the specific project
application only, such as name plates, electrical
distribution, and plumbing. One manufacturer shall
be responsible for the complete Utility Box from
standard frames, trims, covers and enclosures
plus custom internal devices.
1.03
QUALITY ASSURANCE
A. Manufacturer's products shall be listed UL508
sub-panel assembly, ETL 3042374 and IAPMO.
B. The equipment specified herein shall be the
coordinated product of a single manufacturer.
All trims, frames, covers, enclosures, electrical,
plumbing and cabinet fabrication must be furnished
by one single manufacturer.
C. Manufacturer shall supply full testing documentation
required by the specifying engineer for structural,
electrical, and plumbing. Box cover design shall
be certified and stamped by a structural engineer.
D. All floor boxes must be manufactured and installed
in such a manner to allow the floor box to be
removed from the floor and replaced without having
to saw-cut concrete.
1.04
WARRANTY
All equipment shall be warranted free of defects
in materials and workmanship for a period of eighteen
(18) months from date of shipment or one year
from date of turn-on, whichever occurs first.
1.05 MANUFACTURER
Box shall be the standard product of a company
regularly engaged in the manufacture of combined
utilities boxes. Contents of the box may be customized
to suit, subject to limitations of box dimensions.
Boxes shall be manufactured by Combined Utilities
Box Systems (805/532-1776), 5325 North Commerce
Ave., #4, Moorpark. CA 93021-1643. Only one manufacturer
known to specifying agency.
PART 2 - PRODUCT
(Back
to Menu)
2.01 MANUFACTURER'S REQUIREMENTS
A. The equipment herein specified is manufactured
by Combined Utility Box Systems (CUBS), Moorpark
California, (805/532-1776) and shall serve to
indicate the quality of equipment required. Base
bid shall be for the equipment by CUBS. If alternate
equipment is proposed, it shall be shown as an
add or deduct from the base bid price and shall
be subject to approval.
B. Other manufacturers who wish to bid must submit
a complete bill of materials, company information,
and certified test results listing qualifications
to the Architect ten (10) days prior to bid. Bid
approval signed by the Architect must be supplied
at the time of bid. All other manufactures must
comply with the bid specifications.
2.02
SYSTEM TESTING
A. The lid shall be capable of bearing the following
loading conditions for 20 minutes without permanent
deformation:
1. A solid tire fork lift with a lifting capacity
of 30,000 pounds and a dead weight of 34,000 pounds.
The maximum total load on the two front wheels
is 64,000 pounds and on one wheel is 32,000 pounds.
The assumed foot print is 16 inches by 1 inch.
2. A six wheel pneumatic tired vehicle with a
lifting capacity of 62,000 pounds and a dead load
weight of 80,600 pounds. The maximum total load
on four front wheels is 142,600 pounds and on
one wheel is 35,650 pounds. The assumed foot print
is 16 inches by 15 inches, based on 150 P.S.I.
tire pressure. The dual wheels are spaced 20 inches
on center.
3. Minimum safety factor: 1.65.
4. Minimum load rating for the lid on Type "A",
"B", "C" or "M"
box shall be 32,000 pounds.
2.03
UTILITY BOXES
A. TRIM: ("A", "B"
& "C")
1. The Trim shall be fabricated from 1/4"
carbon steel, ASTM A36
2. Hot dip galvanize trim after fabrication.
3. Trim shall have hold down anchor holes to secure
the frame during the concrete pour.
B. FRAME: ("A", "B"
& "C")
1. A cast, A356-T6 aluminum frame shall mount
flush with the trim, cover, and floor.
2. The finish is to be sand cast with flat square
pattern. Groves to form the pattern, should be
1/16" x 1/16" cross sections, spaced
1/2" apart.
3. Aluminum castings shall be Aluminum Association
No. A356-T6 minimum with a yield stress of 20,000
PSI minimum.
C. COVER: (All Boxes)
1. Covers shall be cast, A356-T6 aluminum.
2. Finish shall be the same grooved, square pattern
as the frame. Patterns shall be continuous.
3. Maximum weight is 37 pounds.
4. Each cover shall have two cable doors and one
self-retracting inside/outside handle, Type "A"
box and Type "C" box has 2 covers.
5. Mating surfaces shall be gasketed. ("A",
"B" & "C")
6. Aluminum castings shall be Aluminum Association
No. A356-T6 minimum with a yield stress of 20,000
PSI minimum.
7. Covers will have double handles that will operate
from the interior and exterior of the cover depending
on if the cover is open or closed.
8. Cable access doors shall have break away friction
hinges that will keep them in either open or closed
position when the cover is opened.
9. Covers, when opened, shall allow full access
to plug devices without obstruction of the cover's
frame.
10. Covers shall not be able to be removed from
the frames. Covers must be able to be fully closed
even when devices have been plugged-in. Covers
that require their removal when in use will not
be allowed, exception type "M".
11. Covers shall interlock for added strength
and safety.
D. ENCLOSURE:
1. Box shall be fabricated from 3/8" PVC
or 304 Stainless Steel.
2. Partitions shall be welded in place to form
watertight joints.
3. Openings in box shall be cut in the field by
others.
4. Box shall be removable after installed in the
concrete without having to cut the concrete. Removal
demonstration shall be required by the Specifying
Engineer prior to approval.
E. DEAD FRONT:
1. Dead front sub-panel for electrical components
shall be fabricated from 304 stainless steel.
2. Dead fronts shall be held in place by captive
screws.
3. All devices on dead fronts shall be furnished
with gasketed covers.
F. ASSEMBLY:
1. Finished assembly of trim, frame and covers
are to be flat and level with the floor within
1/8".
2. Sub-panels fasteners shall be captive stainless
steel.
3. Gaskets shall be 1/8" thick neoprene (30
durometers) and resistant to oil, acids, abrasive,
aging and oxidation. Gaskets to be held in place
with adhesive.
4. Nameplates shall be white with black letters.
5. Each receptacle and each breaker shall be labeled
with amperage and phases per IEEE recommended
practice.
2.04
ELECTRICAL
A. DEVICES:
1. Electrical components shall be U.L. Listed.
2. Sub-panels shall be pre-wired prior to shipping
and U.L. Listed (UL508).
3. Minimum 10,000 AIC, RMS.
4. Lugs rated minimum 75°C.
B. WIRING:
1. Wiring shall be 75°C THWN or XHHW.
2. Color code:
a. Ground - Green
b. Neutral - White or Grey
c. A phase - Black
d. B phase - Red
e. C phase - Blue
C. BREAKERS: (as noted on the drawings)
1. 30A, 3 pole, 240 VAC molded case, panel mount,
reversible lugs, weather resistant cover.
2. 20A, 3 pole, 240 VAC molded case, panel mount,
reversible lugs, weather resistant cover.
3. 20A, 1 pole, 120 VAC molded case, panel mount,
reversible lugs, weather resistant cover.
D. RECEPTACLES: (as noted on the drawings)
1. 150A, 208Y/120V, 5-wire, load make, load break,
dead front mount, weather resistant cover.
2. 30A, 208Y/120V, 5-wire, locking panel mount,
NEMA L21-30R, with cover.
3. 20A, 208Y/120V, 5-wire, locking panel mount,
NEMA L21-20R, with cover.
4. 20A, 125V, GFI, duplex grounding, 3-wire panel
mount, heavy duty, NEMA 5-20R,.
E. POWER BLOCKS: (as noted on the drawings)
1. 600V rated.
2. One piece electrical continuity.
3. Tin plated 6061-T6.
4. 90°C.
5. Single barrel primary entry, size up to AWG
#2/0.
6. Six barrel secondary entry, size AWG #14 to
#4.
2.05
TELECOMMUNICATIONS:
A. DEVICES: (as noted on the drawings)
1. Category V, triplex, RJR-45 connectors, with
cover.
2. Type SC, simplex connector, multimode fiber
optic.
3. Cover.
B. WIRING:
1. Wring by others.
2.06 PLUMBING: (as noted on the drawings)
A. FITTINGS:
1. Bulkhead connector, 1/2" MNPT x 1/2"
MNPT, 316 stainless steel.
2. Nipple, close, 1/2".
3. Nipple, close, 1/2".
4. Bushings, 1/2"FNPTx1/2"FNPT.
B. VALVES:
1. Ball.
2. 1/2".
3. 200 PSIG, WOG.
4. Teflon seats.
5. Adjustable packing gland.
6. Removable lever.
7. Minimum Cv of 25.
C. REGULATOR: (If Required)
1. 1/2"NPT
2. 0 to 125 psig.
3. Maximum supply pressure 300 psig.
4. 1/4" gauge port and gauge.
D. QUICK CONNECTS:
1. Female, 1/2".
2. Industrial interchange series B.
3. Stainless steel.
4. ISO standard 7241/1 Series B.
5. Buna-N seals.
E. DRAIN:
1. 3" PVC, domed strainer for main drain.
2. 1-1/4" stainless steel, flat strainer
for auxiliaries.
PART 3 - EXECUTION
(Back
to Menu)
3.01
INSTALLATION:
Boxes shall be installed by others. Competent
trades people from several trades are required
to coordinate the installation. Responsibility
for design and installation of electrical, low
voltage and wet systems beyond the limits of the
box supplied is by others. Care must be taken
not to damage the box or associated conduit and
piping systems. Temporary covers for use during
construction shall be supplied by others. Installation
requirements by the manufacturer need to be coordinated
to insure overall function and operation of the
floor boxes.
3.02 O&M MANUALS:
Upon completion, provide documentation consisting
of engineering test reports, drawings, bill of
materials, and spare parts list. Provide additional
list of optional items, not part of this contract,
that may be used in conjunction with the utility
boxes such multi-outlet supplies, extension cables,
male connectors for 150A, 30A, 20A wiring devices,
water extender valve, etc.
|